Main specs
-
-
-
Manufacturer Part Number
HCTR10
-
Specification
-
-
-
-
Rejection/Non-Rejection
Rejection
-
-
-
-
-
-
Body Size
0.41 in Dia x 1.5 in L
-
Features
-
The HCTR was designed to meet the needs of control circuit transformer protection
-
Current limitation protects down stream components against damaging thermal and magnetic effects of short circuit currents
-
HCTR fuses meet the UL 508, paragraph 19.2.4 requirement that control circuit fuses used in equipment listed for use with more than 10 kA available must have an adequate interrupt rating and must be rejection type
-
High inrush time delay
-
Control circuit transformers can experience inrush currents up to 85 times their full load current rating
-
HCTR fuses can be sized according to NEC and UL requirements and still allow the high inrush currents, with significantly more time delay than the UL minimum value of 12 sec at 200% for class CC fuses
-
Melamine tube with nickel plated bronze endcap
Additional Information
-
Alternative Part Number
8430176
-
-
-
-
Standards/Approvals
UL Listed ,CSA Certified,CE Marked,RoHS Compliant
Reviews
There are yet no reviews for this product.
Please log in to write a review.