Littelfuse® POWR-GARD® Slo-Blo® 229003P Time Lag Cartridge Fuse, 3 A, 250 V AC, 10 kA Interrupt, Class: RK1, Cartridge Body

0 Ratings
$1.13
In Stock
SKU: LIT229003
GTIN (EAN,ISBN): 00079458915501
noimage_new

Littelfuse® 229/230 series Slo-Blo® fuses are available in 2AG size cartridge or axial lead form, offer tripped fuse indicating option, and offer features designed to meet rigorous Telecom industry requirements. 229/230 series product ordered with the tripped fuse indicating option show discoloration of the glass body immediately after trip. They offer the same performance characteristics as standard product and help to reduce time locating the tripped fuse and troubleshooting circuit issues. The 229/230 series 0.25 to 1.25 A range combines conventional over current protection with ability to withstand high current, short duration pulses which complies to short circuit requirements of UL 60950 for telephone equipment. Insulating sleeve option is also available.

In Stock
HCI of Jackson: 49
HCI of Dyersburg: 9
HCI of Humboldt: 9
HCI of Union City: 9
HCI of Gallatin: 9
My Wishlist
Compare
Main specs
  • Brand
    Littelfuse®
  • UPC
    079458915501
  • Manufacturer Part Number
    229003P
  • Country
    USA
Specification
  • Terminal Type
    Ferrule
  • Material
    Glass
  • Class
    RK1
  • Response Time
    4 hr, 1 hr, 3 to 20 s
  • Type
    Time Lag
  • Mounting Type
    Holder
  • Voltage Rating
    250 V AC
  • Amperage Rating
    3 A
  • Series
    229
  • Indicating/Non-Indicating
    Indicating
  • Interrupt Rating
    10 kA
  • Body Size
    5 mm Dia x 15 mm L
  • Body Type
    Cartridge
Features
  • Offer the same performance characteristics as standard product, and help to reduce time locating the tripped fuse and troubleshooting circuit issues
  • Combines conventional over current protection with ability to withstand high current, short duration pulses
  • -60 to 125 deg C operating temperature
  • 0.0383 ohms resistance
  • 77 I2T (A2 sec) nominal melting
  • 10 kA at 125 VAC interrupting rating
  • Tripped fuse indicating
  • 4 hrs minimum at 100%, 1 hr maximum at 135%, 3 to 20 sec maximum at 200% response time
  • Glass body, nickel plated brass end cap
  • Size 2AG
Additional Information
  • Alternative Part Number
    0229003.VXP|9533885
  • UNSPSC
    39121627
  • IDEA Index ID
    9533885
  • Package Description
    EACH
  • Standards/Approvals
    UL 248-12|CSA Certified|PROP65: This product can expose you to chemicals including nickel, which is known to the State of California to cause cancer
Attachments
Reviews

There are yet no reviews for this product.