Main specs
-
-
-
Manufacturer Part Number
313.500P
-
Specification
-
-
-
-
Response Time
4 hr, 1 hr, 5 to 30 s
-
-
-
-
-
-
Indicating/Non-Indicating
Non-Indicating
-
-
Body Size
1/4 in Dia x 1-1/4 in L
-
Features
-
Time delayed in the overload range, which provides superior protection inductive loads such as motors, transformers and solenoids
-
3AG Indicating fuses instantly identify themselves upon opening by showing a discoloration of their glass bodies
-
Guesswork and time consuming circuit testing is eliminated
-
Unique design offers the same quality performance characteristics as the standard 3AG fuse design
-
Lead-free
-
Nickel plated brass cap
-
-55 to 125 deg C operating temperature
-
10 kA at 125 VAC interrupting rating
-
4 hrs minimum at 100%, 1 hr maximum at 135% and 5 to 30 sec maximum at 200% opening time
-
1.26 ohms nominal cold resistance
-
2.55 I2T (A2 sec) nominal melting
Additional Information
-
Alternative Part Number
0313.500VXP|9533991
-
-
-
-
Standards/Approvals
UL 248-12|UL File No. E10480|CSA 29862|PROP65: This product can expose you to chemicals including nickel, which is known to the State of California to cause cancer