Main specs
-
-
-
Manufacturer Part Number
ECNR80
-
Specification
-
-
-
-
Rejection/Non-Rejection
Rejection
-
Response Time
10 s at 500%
-
Type
Current Limiting Time Delay
-
Voltage Rating
250 V AC/125 V DC
-
-
-
Indicating/Non-Indicating
Non-Indicating
-
Interrupt Rating
200 kAIC
-
Body Size
1.06 in Dia x 5.88 in L
-
-
Features
-
Provides motor overload, ground fault and short circuit protection
-
Helps protect motors against burnout from 1 ph on 3 ph systems
-
Simplifies and improves blackout prevention (selective co-ordination ratios)
-
Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
-
The overload element provides protection against low level overcurrent of overloads and will hold an overload which is 5X greater than the amperage rating of the fuse for a minimum of 10 s
-
Superior overload and cycling capabilities
-
True dual element construction allows sizing of 125% FLA for motor backup protection
-
Current limiting provides component short circuit protection
-
For all general purpose applications including lighting, heating and other non-inductive loads
-
Tin plated copper brass terminal and zinc plated steel screws
Additional Information
-
Alternative Part Number
11197141
-
-
-
-
Standards/Approvals
CE Marked
Reviews
There are yet no reviews for this product.
Please log in to write a review.